PIERCING CONNECTOR – INSULATED MAINS
APPLICATION
Mains: Insulated copper or aluminium
Tap: Insulated copper or aluminium
FEATURES
Provides a fully sealed, waterproof connection on the tap.
No need to strip cable to make the connection
Simultaneous piercing on main & tap
Torque controlling shear heads on all bolts
Tightening bolts do not come into contact with live components
Captive end cap for protection of tap cable, which can be mounted on either side.
Fully bimetallic
Stainless steel fasteners
INSTALLATION NOTES
When using 2 bolt connectors from this range, each bolt must be tightened a 1/4 to 1/2 turn alternately, until the shear head operates.
For tightening the shear head bolts, use only a 13mm AF, six sided hexagon socket (17mm AF for models NTD431XFA and NTD451XFA).
For double insulated cables, the outer sheath should be removed before applying the connector.
PARTS: TTD051XFA, TTD101NBKXE, TTD101XFA, TTD101XFAE, TTD151XFA, TTD151XFAE, TTD201XFA, TTD201XFAE, TTD241XFAE, TTD271XFAE, TTD301XFA, TTD301XFAE, TTD351XFA, TTD351XFAE, TTD401XFA, TTD401XFAE, TTD431XFA, TTD431XFAE, TTD451XFA
Mains | 06mm – 54mm, 16mm – 95mm, 25mm – 95mm, 35mm – 95mm, 50mm – 150mm, 50mm – 185mm, 70mm – 240mm, 95mm – 240mm |
---|---|
Service | 01.5mm – 10mm, 06mm – 35mm, 16mm – 95mm, 25mm – 95mm, 35mm – 95mm, 50mm – 150mm, 95mm – 240mm |